Overview
GGD type AC low-voltage power distribution cabinet is suitable for power distribution systems with AC 50Hz, rated working voltage of 380V, and rated working current of 5000A for power users, such as power plants, substations, industrial and mining enterprises, as power conversion, lighting and power distribution equipment. for distribution and control.
The product has the characteristics of high breaking capacity, good dynamic and thermal stability, flexible electrical scheme, convenient combination, strong practicability, novel structure and high protection level. It can be used as a replacement product for low-voltage switchgear.
GGD type AC low-voltage power distribution cabinet complies with IEC439 “Low-voltage switchgear and control equipment”, GB7251 “Low-voltage switchgear” and other standards.
Model Meaning
Functions and Features
◆The ambient air temperature should not be higher than +40℃ and not lower than -5℃. The average temperature within 24h shall not be higher than +35℃.
◆Indoor installation and use, the altitude of the place of use shall not exceed 2000m.
◆The relative humidity of the surrounding air does not exceed 50% when the maximum temperature is +40℃, and a relatively large relative humidity is allowed when the temperature is lower. (eg 90% at +20°C) The effect of condensation that may occasionally occur due to temperature changes should be considered.
◆When the equipment is installed, the inclination from the vertical plane should not exceed 5%.
◆The equipment should be installed in a place without severe vibration and shock, and a place that is not enough to cause corrosion of electrical components.
◆When users have special requirements, negotiate with the manufacturer.
Electrical properties
Model |
Rated voltage (V) |
Rated current (A) |
Rated short-circuit breaking current (kA) |
Rated short-time withstand current (1 S) (kA) |
Rated peak withstand current (kA) |
GGD1 |
380 |
A1000 |
15 |
15 |
30 |
GGD2 |
380 |
B600(630) |
30 |
30 |
63 |
GGD3 |
380 |
C400 |
50 |
50 |
105 |
GGD1 |
380 |
A150O(1600) |
15 |
15 |
30 |
GGD1 |
380 |
B1000 |
15 |
15 |
30 |
GGD2 |
380 |
C600 |
30 |
30 |
63 |
GGD2 |
380 |
A3200 |
30 |
30 |
63 |
GGD3 |
380 |
B2500 |
50 |
50 |
105 |
GGD3 |
380 |
c2000 |
50 |
50 |
105 |