Model Meaning
Functions and Features
◆Cabinet body is welded with high-quality angle steel.
◆The circuit breaker room is located in the middle (lower) part of the cabinet, which is convenient for installation, debugging and maintenance. Standard equipped with VS1 circuit breaker, and has a pressure release channel to ensure personal safety.
◆Adopt advanced and reliable rotary isolating switch, which can safely enter the circuit breaker room for maintenance when the main bus is live.
◆The protection grade of the whole cabinet is IP2X.
◆It is equipped with a reliable and complete mandatory mechanical locking device, which can easily and effectively meet the requirements of “five preventions”.
◆Have a reliable grounding system.
◆The door is equipped with an observation window, which can clearly observe the working state of the components in the cabinet.
◆The locking mechanism of the operating mechanism adopts the same JSXGN locking mechanism used in the XGN2-12 cabinet, which is simple, reliable, convenient and practical.
◆Incoming and outgoing cables are lower than the front of the cabinet, which is convenient for users to connect.
The main technical parameters
Serial number |
Project |
Unit |
FN12-10 |
FZN25-12 |
|
1 |
Rated voltage |
kV |
12 |
||
2 |
1min power frequency withstand voltage |
Hz |
Ground and phase 42; isolation fracture 48 |
||
3 |
Lightning impulse voltage (peak) |
A |
Ground and interphase 75; isolation fracture 85 |
||
4 |
Rated frequency |
times |
50 |
||
5 |
Main busbar rated current |
kVA |
630 |
||
6 |
load switch |
Rated current |
kA/s |
630 |
|
7 |
Power-off life at rated current |
kA |
not less than 100 |
||
8 |
Breaking no-load transformer capacity |
kV |
1250 |
||
9 |
Rated thermal stability current |
kV |
20/4; earthing switch 20/2 |
||
10 |
Rated dynamic stable current (peak value) |
A |
50 |
||
11 |
Rated short-circuit making current (peak value) |
kA |
50 |