Overview
GCS low-voltage withdrawable switchgear is suitable for power distribution systems in power plants, petroleum, chemical, metallurgy, textile, high-rise buildings and other industries. In large power plants, petrochemical systems and other places with a high degree of automation and requiring interface with computers, it can be used as a power generation and power supply system with a three-phase AC frequency of 50 (60) Hz, a rated working voltage of 400V, 660V, and a rated current of 5000A and below. A low-voltage complete set of power distribution devices used in power distribution, motor centralized control, and reactive power compensation. The design of the device complies with the following standards: IEC439-1 “Low-voltage switchgear and control equipment” GB7251 “Low-voltage switchgear”.
Model Meaning
Normal use environment
◆The ambient air temperature should not be higher than +40℃, not lower than -5℃, and the average temperature within 24 hours should not be higher than +35℃. When it exceeds, the derating operation shall be performed according to the actual situation;
◆For indoor use, the altitude of the place of use shall not exceed 2000m;
◆The relative humidity of the surrounding air does not exceed 50% when the maximum temperature is +40°C, and a relatively large relative humidity is allowed at a lower temperature, such as 90% at +20°C. produce condensation effects;
◆When the device is installed, the inclination of the vertical plane should not exceed 5°, and the entire group of cabinets should be relatively flat (in line with GBJ232-82 standard);
◆The device should be installed in a place without severe vibration and shock and not enough to cause the electrical components to be corroded;
◆When users have special requirements, they can negotiate with the manufacturer.
The main technical parameters
Serial number |
Rated current (A) |
Parameter |
|
1 |
Main circuit rated voltage (V) |
AC 400/660 |
|
2 |
Auxiliary circuit rated voltage |
AC 220, 380 (400), DC 110, 220 |
|
3 |
Rated frequency(Hz) |
50(60) |
|
4 |
Rated insulation voltage (V) |
660 |
|
5 |
Rated current (A) |
Horizontal busbar |
≤5000 |
Vertical Busbar (MCC) |
1000 |
||
6 |
Busbar rated peak withstand current (KA/0.1s) |
50.8 |
|
7 |
Busbar rated peak withstand current (KA/0.1s) |
105,176 |
|
8 |
Power frequency test voltage (V/1min) |
The main circuit |
2500 |
Auxiliary circuit |
2000 |
||
9 |
busbar |
Three-phase four-wire system |
A.B.C.PEN |
Three-phase five-wire system |
A.B.C.PE.N |
||
10 |
Protection class |
IP30.IP40 |