Overview
ZN63(VS1)-12 series indoor high-voltage vacuum circuit breaker is an indoor high-voltage switchgear, suitable for three-phase power system with rated voltage of 12kV and frequency of 50Hz. It is used as protection and control electrical appliances. Excellent performance, especially suitable for places that require frequent operation at rated current, or break short-circuit current many times.
ZN63(VS1)-12 series side-mounted vacuum circuit breaker adopts fixed installation and is mainly used for fixed switch cabinet. system.
Normal Use Conditions
◆ Ambient temperature: – 10 ℃ to 40 ℃ (storage and transportation at – 30 ℃ are allowed).
◆ Altitude: generally not more than 1000m. (If it is necessary to increase the altitude, the rated insulation level will increase accordingly)
◆ Relative humidity: under normal conditions, the daily average is not more than 95%, the daily average saturated steam pressure is MPa, and the monthly average is not more than 1.8 × ten
◆ Seismic intensity: not more than 8 degrees under normal conditions.
◆ It can only be used in places without fire, explosion, serious pollution, chemical corrosion and serious vibration.
The Main Technical Parameters
Serial number |
Name |
Units |
Data |
|||
1 |
Rated voltage |
kV |
12 |
|||
2 |
Maximum working voltage |
kV |
12 |
|||
3 |
Rated current |
A |
630 |
630 1250 |
1250 1600 |
|
4 |
Rated short-circuit breaking current (rated thermally stable current – RMS) |
kA |
20/25 |
31.5 |
40 |
|
5 |
Rated short-circuit making current (peak value) |
kA |
50/63 |
80 |
100 |
|
6 |
Rated peak withstand current (rated dynamic stable current – peak value) |
kA |
50/63 |
80 |
100 |
|
7 |
4S rated short-circuit withstand current |
kA |
20/25 |
31.5 |
40 |
|
8 |
Rated insulation level |
Working withstand voltage (before and after rated breaking) 1 min power frequency withstand voltage |
kv |
Ground 42 (fracture 48) |
||
Impulse withstand voltage (before and after rated breaking) Rated lightning impulse withstand voltage peak value |
Ground 75 (fracture 85) |
|||||
9 |
Rated thermal stabilization time |
s |
4 |
|||
10 |
Nominal Operation Sequence |
Score – 0.3S – Combined – 180S – Combined |
||||
11 |
Mechanical life |
times |
20000 |
|||
12 |
Rated short-circuit breaking current breaking times |
times |
50 |
|||
13 |
Operating mechanism rated closing voltage (DC) |
v |
AC . DC 110,220 |
|||
14 |
Operating mechanism rated opening voltage (DC) |
v |
AC . DC 110,220 |
|||
15 |
Contact Spacing |
mm |
11±1 |
|||
16 |
Overtravel (contact spring compression length) |
mm |
3.5±0.5 |
|||
17 |
Three-phase opening and closing bounce time |
ms |
≤2 |
|||
18 |
Contact closing bounce time |
ms |
≤2 |
|||
19 |
Average opening speed |
m/s |
0.9~1.2 |
|||
Average closing speed |
m/s |
0.5~0.8 |
||||
20 |
Opening time |
at the highest operating voltage |
s |
≤0.05 |
||
21 |
at minimum operating voltage |
≤0.08 |
||||
22 |
Closing time |
s |
0.1 |
|||
23 |
Main circuit resistance of each phase |
υ Ω |
630≤50 1250≤45 |
|||
24 |
The dynamic and static contacts allow the accumulated thickness of wear |
mm |
3 |