Overview
ZW32ABG-12 outdoor high-voltage permanent magnet vacuum circuit breaker (hereinafter referred to as permanent magnet switch) is an outdoor high-voltage switchgear with three-phase AC 50Hz and rated voltage of 12kV. The permanent magnet switch is mainly used as a 10kV outgoing switch in a substation and a 10kV three-phase AC power system as a line protection switch for splitting and combining load current, breaking overload current and short-circuit current.
The circuit breaker conforms to the technical standards such as GB1984-2003 “High Voltage AC Circuit Breaker”, DL/T402-2007 “High Voltage AC Circuit Breaker Ordering Technical Conditions” and DL/T403-2000 “12kV-40.5 High Voltage Vacuum Circuit Breaker Ordering Technical Conditions”.
Normal Use Conditions
◆Ambient temperature: -40℃~+40℃; Altitude: 2000m and below;
◆The surrounding air can be polluted by dust, smoke, corrosive gas, steam or salt mist, and the pollution level is the target level;
◆The wind speed does not exceed 34m/s (equivalent to 700Pa on the cylindrical surface);
◆Special conditions of use: The circuit breaker can be used under normal conditions different from those specified above. Please negotiate with us for special requirements.
The Main Technical Parameters
Serial number |
Project |
Unit |
Parameters |
1 |
Rated voltage |
KV |
12 |
2 |
Rated frequency |
Hz |
50 |
3 |
Rated current |
A |
630 |
4 |
Rated short-circuit breaking current |
KA |
20 |
5 |
Rated peak withstand current (peak) |
KA |
50 |
6 |
Rated short-time withstand current |
KA |
20 |
7 |
Rated short-circuit making current (peak value) |
KA |
50 |
8 |
Mechanical life |
times |
10000 |
9 |
Rated short-circuit breaking current breaking times |
times |
30 |
10 |
Power frequency withstand voltage ( 1min): (wet) (dry) phase-to-phase, to ground/fracture |
KV |
42/48 |
11 |
Lightning impulse withstand voltage (peak value) phase-to-phase, to ground/fracture |
KV |
75/85 |
12 |
Secondary circuit 1min power frequency withstand voltage |
KV |
2 |