Overview
ZW8-12 outdoor high-voltage vacuum circuit breaker, three-phase AC 50Hz outdoor high-voltage switchgear. It is composed of operation, conductive circuit, insulation system, seal and shell, and the overall structure is three-phase common box type. It is used for 10kV rural power grid and urban power grid power system, as split, combined load current, overload current, short-circuit current and other similar places.
Implement the standard GB1984-2003 "High Voltage AC Circuit Breaker" GB/T11022-1999 "Common Technical Requirements for High Voltage Switchgear and Control Equipment Standards" IEC62271-100 "High Voltage AC Circuit Breaker"
Normal Use Conditions
◆Ambient temperature: -40℃~+40℃;
◆Altitude: ≤3000m (if the altitude increases, the rated insulation level will increase accordingly);
◆The surrounding air can be polluted by dust, smoke, corrosive gas, steam or salt spray, and the pollution level is IV;
◆The wind speed does not exceed 34m/s (equivalent to 700Pa on the cylindrical surface);
◆Vibration or ground motion from outside of switchgear and control equipment can be ignored;
◆Special conditions of use. (If you need to apply it under normal conditions of use different from the above, please negotiate with us).
The Main Technical Parameters
Serial number |
Name |
Unit |
Data |
|
1 |
Rated voltage |
kV |
12 |
|
2 |
Rated current |
A |
630 1250 |
|
3 |
Power frequency dry withstand voltage (1min) |
kV |
42 |
|
4 |
Lightning impulse withstand voltage (peak) |
75 |
||
5 |
Rated short-circuit breaking current |
kA |
16 20 25 |
|
6 |
Rated short-circuit making current |
|
40 50 63 |
|
7 |
Rated peak withstand current |
kA |
40 50 63 |
|
8 |
4s short-time withstand current |
|
16 20 25 |
|
9 |
Nominal Operation Sequence |
|
Points-0.3s-Combined points-18Os-Combined points |
|
10 |
Rated short-circuit current breaking times |
times |
30 |
|
11 |
Mechanical life |
|||
Rated voltage of energy storage motor |
times |
|||
12 |
Rated operating voltage Opening coil |
V |
DCorAC 220 |
|
Equipped with special spring operating mechanism Closing coil |
V |
DCorAC 220 |
||
13 |
Rated current of overcurrent release |
A |
5 |
|
14 |
Allowable wear thickness of static and dynamic contacts |
mm |
3 |
|
15 |
Contact Spacing |
mm |
11±1 |
|
16 |
Overtravel (contact spring compression length) |
mm |
+1.0 |
|
17 |
Three-pole closing and opening of different periods |
ms |
≤2 |
|
18 |
Contact closing bounce time |
ms |
≤2 |
|
19 |
Average opening speed |
m/s |
1.0±0.2 |
|
20 |
Average closing speed |
m/s |
0.7±0.15 |
|
21 |
Opening time |
at the highest operating voltage |
s |
0.015-0.05 |
at minimum operating voltage |
s |
0.03-0.06 |
||
22 |
when closing |
s |
0.025-0.05 |
|
23 |
Main circuit resistance |
μΩ |
≤120(with G≤200) |